電力品質監視器含衛星時間

  • 型號 / 1133A
  • 廠牌 / Arbiter
  • IEEE C37.118 PMU兼容裝置
    經由內置GPS衛星進行同步接收
    支援同步領先市場
    接收精度:0.025%
    電力品質:諧波,閃爍,干擾分析
    對於穩定性和流場分析之相量測量
    具系統時間和頻率偏移
    內部資料及故障事件記錄
    原購者具兩年保修

檔案下載 /

/ 詳細規格 /
標準電壓:85 VAC至264 VAC,47赫茲至63赫茲或120伏到275伏,5 VA典型
環境溫度:
工作: - 10°C至+ 50°C
非工作: - 40°C至+ 85°C
濕度:非冷凝
尺寸:430毫米(寬)點¯x44毫米高x260毫米深
重量:2公斤(4.5磅),淨
同步輸出:IRIG-張使用B 200 mA峰值
協議:專有功率哨兵CSV(PSCSV)
標準:DNP3.0,MODBUS,PQ-DIF,IEEE C37.118

通訊 :串行端口1
RJ-11連接器模塊
RS-232(1133opt10)
RS-422/485半雙工(1133opt11)
調製解調器(V.34bis,33.6K)(1133opt12)
 
串行端口2
RJ-11連接器模塊
RS-232(1133opt20)
RS-422/485半雙工(1133opt21)
調製解調器(V.34bis,33.6K)(1133opt22)

以太網連接器
RJ-45連接器
IEEE802.3i 10 Base-T
 

Input/Output

Configuration

3 Ø:

3-element, 2½-element, 2-element, selectable

1 Ø:

2-element, 1½-element, and 1-element, selectable

Voltage

Range (3 Ø/1 Ø)

0 Vrms to 69 Vrms, 120 Vrms, 240 Vrms, or 480 Vrms, selectable (phase-to-phase for 2 element; phase-to-neutral for 2½ element and 3 element)

Overrange

88 Vrms, 175 Vrms, 350 Vrms, or 700 Vrms, nominal

Current

Range (3 Ø/1 Ø)

2.5 Arms, 5 Arms, 10 Arms, or 20 Arms, selectable, per element

Overrange

2.9 Arms, 5.9 Arms, 11.7 Arms, or 23.5 Arms, nominal (maximum continuous input current: 20 Arms per element)

VA, W, VAR

Range

Product of rated voltage and current ranges and number of elements (2½ (3 Ø) and 1½ (1 Ø) element, use 3 and 1, respectively)

Compensation

CT and PT

Both magnitude and phase compensation, CT with 12 point nonlinear interpolation

Transformer

Both iron and copper compensation

Frequency

Range

45 Hz to 65 Hz, for specified accuracy

Harmonics

To 3 kHz

Inputs

Insulation

400 volts, nominal, to neutral/chassis, surge voltage class III
600 volts, nominal, to neutral/chassis, surge voltage class II

Contact Technical Support for more detailed information

Connections

Removable screw-clamp terminal block, accepting 0.2 mm to 4 mm2 (#24 to #10 AWG) solid or stranded conductors

Power Quality

Harmonics Measurement

Standard

Per IEC 61000-4-7, 100 ms overlapping data window

Measurements

THD, K-factor, rms harmonic current and voltage, rms harmonic current and voltage with K-factor compensation (each harmonic magnitude is multiplied by the square of the harmonic number before summing), individual magnitude and phase

Logged Data

Selectable, may be regularly logged or registered; or event-logged when user-specified limits are exceeded

Interruptions Logged Data

Selectable, may be regularly logged or registered; or event-logged when user-specified limits are exceeded

Flicker

Standard

Per IEC 61000-4-15, Pst and Instantaneous

Logged Data

Selectable, may be regularly logged or registered; or event-logged when user-specified limits are exceeded

Limit Alarms

Functions

Upper or lower limits may be set on most measured functions. Limits may also be set on maximum imbalance

Output

Via system interface and display or contact closure

Host Processor

Capacity

32 megabytes standard; number of records stored depends on data items selected. See Operation Manual for record length and capacity calculations

Data

Selectable from all functions measured and totalized by the Model 1133A; each record is stored with a time tag

Storage Rate

Selectable; default is 15 minutes. Other intervals as short as one minute may be selected. Event data stored upon occurrence.

Lifetime

100,000 storage cycles minimum

Data Retention

Indefinite; no power or battery is required to retain data

System Control and Monitoring

System Time, Phase and Frequency

System Time

Unlimited accumulation with ± 1 µs resolution

Frequency

7 digits, xx.xxxxx Hz

System Phase

0 ° to 360 ° with 0.01 ° resolution

Effect of DC & Harmonics

None; Rejected by narrow band digital filtering

Phasors

Standard

Per IEEE 1344, IEEE C37.118, or PSCSV

Rate

Selectable: 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60 measurements/second for 60 Hz or 1, 2, 5, 10, 25, 50 measurements/second for 50 Hz. Including df/dt.

Interface

Operator

Status LEDs

Operate (green), Time Set (green), Alarm (red), Fault (red)

Display

2 character x 20 character LCD display

Keyboard

8 key for status and setup

Communications

Serial Port 1

RJ-11 modular connector
RS-232 (1133opt10)
RS-422/485 half-duplex (1133opt11)
Modem (V.34bis, 33.6k) (1133opt12)

Serial Port 2

RJ-11 modular connector
RS-232 (1133opt20)
RS-422/485 half-duplex (1133opt21)
Modem (V.34bis, 33.6k) (1133opt22)

Ethernet Connector

One RJ-45 modular connector
10Base-T per IEEE 802.3i

Protocols

Proprietary

PowerSentinelCSV (PSCSV)

Standard

DNP3.0, MODBUS, PQ-DIF, IEEE C37.118

Programmable Contact Outputs

Type and Number

Form C (SPDT), four (4) sets

Connections

Pluggable 12-pole 5 mm terminal strip, with four, 3-pole mating connectors included

Rating

250 Vac/125 Vdc, 8 A maximum, 2000 VA/150 W maximum

Isolation

4000 Vrms for 1 minute to chassis
Optional KYZ (solid state) contact isolation: 3750 Vrms Input/Output

Functions, Selectable

Programmable Load Control, with preset times or via system interface
Fault Fail-safe (faulted with power off)
Alarm Fail-safe
Out-of-Lock Fail-safe
One Pulse per Hour; contacts closed for one minute at top of hour
Optional KYZ contacts
Other Functions, as required

Event Inputs

Type and Number

Four, optically-isolated 24 Vdc to 240 Vdc (may be configured for 5 volt logic level)

Connections

Pluggable 8-pole 5 mm terminal strip, with four, 2 pole mating connectors

Isolation

4000 Vrms for 1 minute to chassis

Resolution

1 µs

Synchronization

General/Remote

GPS Tracking

GPS-L1 (1575.42 MHz); 12 channel (tracks up to 12 satellites)

GPS Acquisition

2 minutes typical

GPS Accuracy

UTC-USNO ± 1 µs (only need 1 satellite with correct position)

GPS Out of Lock

Via system interface and status

Timebase Error

GPS Locked

Less than 1 µs, when locked to at least one satellite with correct position

Unlocked

10 ppm, typical, after being locked for 10 minutes minimum (< 1 second/day unlocked, typical)

Antenna

Mounting

0.75 in NPT pipe thread (1 in - 14 marine type) mount

Dimensions

80 mm hex (across flats) x 84 mm tall (3.2 in x 3.3 in), including connector

Weight

170g (6.0 oz.)

Connections

F-type

Cable

15 m (50 ft) included; longer cables optionally available

Synchronization Output

IRIG-B

One; IRIG-B000 or IRIG-B003 per IEEE Std. 1344 (unmodulated or level-shift); 200 mA peak; pluggable 5 mm terminal strip with mating connector, two-pole

General

Physical

Size

1 RU (430 mm W x 44 mm H) rack mount or tabletop; 260 mm deep FMS. Rack mounts included.
508 mm x 381 mm x 203 mm (20 in x 15 in x 8 in), shipping

Weight

2 kg (4.5 lbs), net
5.5 kg (12 lbs), shipping

Environmental

Temperature

Operating: - 10 °C to + 50 °C
Nonoperating: - 40 °C to + 85 °C

Humidity

Noncondensing

Power Requirements

External Power

Input

Terminal strip with fuse; surge withstand per ANSI C37-90.1 and IEC801-4 standard

Standard

Voltage

85 Vac to 264 Vac, 47 Hz to 63 Hz or 120 Vdc to 275 Vdc, 5 VA typical